Power mains transient disturbances are the cause of many interferences in electronic equipments. A frequently used protection device is an isolation transformer, which theoretically has very high attenuation to common mode signals between the primary and secondary windings, especially when it is shielded. In practice it is not so efficient, and the background to this is described in the report. A standard measuring circuit for transient damping ability for isolation transformers is proposed. The method will give a better correspondance to the damping normally received in a real installation than the "insertion loss figure", which ignores the cable inductance always present in all installations. It is also proposed that the concept of "transient damping ability" shall refer to free standing protection devices.
SP Rapport 1989:21