WARM AIR HEATING - DESCRIPTION AND EVALUATION OF A ONE-FAMILY HOUSE IN TÄBY. This report examines a well-insulated experimental house in Täby, utilizing warm air heating and an exhaust air heat pump. The house was monitored during 1984-1985. The house has a balanced ventilation system. During the monitoring period, the warm air could be distributed in three different ways to the individual rooms. The main part of the space heating is done by an exhaust air heat pump. The thermal insulation exceeds the requirements of the Swedish Building Code. The windows have a U-value equivalent to a four-pane window. The monitoring has shown that the warm air heating system led to a comfortable indoor climate with fresh air. Occasional high temperatures, which never were above +27 °C, caused by excess "free heat" were recorded. With four-pane windows, a good thermal insulation and airtightness level, the warm air can be blown into the individual rooms from inlets located in the partitions below the ceiling. If the outdoor temperature doesn't fall below a few degrees below the freezing point, three-pane windows are sufficient. During one year the house used 13,000 kWh of electricity for space heating, domestic hot water heating and household use, i.e. approximately half of what a house that meets the current Swedish National Building Code uses. This energy saving was achieved by insulating and tightening the house very well, and installing a heat pump.
SP-RAPP 1986:30
ISSN 0280 - 2503