Two series of model scale tests were conducted to investigate the cooling of smoke using water sprays in tunnel fires, together with a theoretical analysis of the gas cooling efficiency and laboratory water distribution tests for the nozzle at various operating pressures. To exclude the effects of water sprays on the gas phase combustion in the tunnel tests, the water spray section was placed either 1.5 m upstream or downstream of the fire site. The objectives of the study are to quantify the water spray cooling effects in tunnel fires and to provide valuable data for verification of computer modelling of water spray cooling in tunnel fires. Besides, the data are analyzed aiming to obtain some valuable knowledge about the performance of water spray cooling in tunnel fires. The upstream water sprays have been proven to be very effective in control of backlayering smoke, even in case of a 87 MW fire. In most tests, the backlayering front was trapped between the first and second nozzles and only in some tests between the second and third nozzles. The downstream water spray section shows very effective cooling of the smoke flows. A cooling efficiency is defined based on a theoretical analysis. The theory and the test data correlate very well with regard to the effects of tunnel velocity and water flow rate. The results show that the cooling efficiency increases rapidly with the water flow rate, decreases with the heat release rate, and is inversely proportional to the ventilation velocity.
This work was supported by the Tunnel and Underground Safety Center (TUSC)