Influence of selected methodology on derived rise time of partial discharge calibratorsShow others and affiliations
2024 (English)Conference paper, Published paper (Refereed)
Abstract [en]
IEC60270 has recently undergone revision, but the scope for performance tests on calibrators remains largely the same. Three methods are applicable for determination of partial discharge (PD) calibrator charge and risetime numerical integration, passive integration, and active integration. The suitability of each method for determination of charge has been evaluated in EURAMET.EM-S36 Comparison of Partial Discharge Calibrators and is documented in its associated report. However, due to the infeasibility of deriving a comparison reference value for rise time, this metric is omitted from the comparison. Reasons for widely diverging results for rise time derivation are discussed in this paper.
Place, publisher, year, edition, pages
Institute of Electrical and Electronics Engineers Inc. , 2024.
Keywords [en]
Calibration, Active integration, IEC 60270, Numerical integrations, Partial discharge calibrator, Passive integration, Passive/active, Performance tests, Reference values, Risetimes, Integration
National Category
Control Engineering
Identifiers
URN: urn:nbn:se:ri:diva-76040DOI: 10.1109/ICHVE61955.2024.10676201Scopus ID: 2-s2.0-85205694039ISBN: 979-8-3503-7498-8 (print)ISBN: 979-8-3503-7498-8 (electronic)OAI: oai:DiVA.org:ri-76040DiVA, id: diva2:1909636
Conference
2024 IEEE International Conference on High Voltage Engineering and Applications (ICHVE)
2024-10-312024-10-312025-09-23Bibliographically approved