Calibration of the electrochemical methods for the corrosion rate measurement of steel in concrete. Nordtest project 1531-01.
RISE, SP – Sveriges Tekniska Forskningsinstitut, SP Bygg och Mekanik.
2002 (English)Report (Refereed)
Abstract [en]

This report presents the results from the Nordtest project No. 1531-01. In this study, steel bars were embedded in concrete slabs with different chloride introductions (0%, 1.5%, 3% and 6 % by mass of cement) in order to induce corrosion at different rates. The slabs were cast in one laboratory and distributed to three different laboratories for monitoring of corrosion rate over a period of one year. Four instruments representing two types of electrochemical techniques, that is, linear polarisation technique (GECOR instruments) and galvanostatic pulse technique (GalvaPulse and SP’s instrument), were evaluated in the project through the comparative measurements. Finally, the standard gravimetric method ASTM G1 was used for calibration of the results measured by the non-destructive methods based on the electrochemical techniques. The results show that the three different laboratories measured fairly comparable corrosion rates based on the gravimetric method, indicating that the method used in the project for production of specimens is basically suitable for use in the calibration of any type of non-destructive electrochemical techniques for measuring the corrosion rate of steel in concrete. The corrosion rates measured by GECOR are fairly close to the true mean corrosion rate (mass loss divided by the whole exposed area of steel), while the corrosion rates obtained by the 5 seconds short time galvanostatic pulse measurements from the chloride introduced specimens are close to the true actual corrosion rate (mass loss divided by the corroded area of steel). When multiplying the values measured by GECOR by a factor of 6 (as a pitting factor) for the chloride introduced specimens, the re-calculated corrosion rates become very comparable with the true actual corrosion rate. The condition of chloride content in concrete is necessary information for proper judgement of passive or de-passive status of steel when using pulse techniques and proper use of pitting factor when using GECOR instruments.

Place, publisher, year, edition, pages
2002. , 54 p.
Series
SP Rapport, ISSN 0284-5172 ; 2002:25
National Category
Natural Sciences
Identifiers
URN: urn:nbn:se:ri:diva-4579Local ID: 1905ISBN: 91-7848-916-4 (print)OAI: oai:DiVA.org:ri-4579DiVA: diva2:962217
Note
Pris: 150SEK. Beställes via BiblioteketBoras@sp.seAvailable from: 2016-09-07 Created: 2016-09-07Bibliographically approved

Open Access in DiVA

fulltext(1588 kB)23 downloads
File information
File name FULLTEXT01.pdfFile size 1588 kBChecksum SHA-512
52409cda8c1496dddbf6d9b93570bf8a6565a8bfb59c2302cc2384dc2bc205fe25bb4cec85ea744299a980a387fd1fda28c23bd82003deaa1a677427c062e9c8
Type fulltextMimetype application/pdf

By organisation
SP Bygg och Mekanik
Natural Sciences

Search outside of DiVA

GoogleGoogle Scholar
Total: 23 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

Total: 68 hits
CiteExportLink to record
Permanent link

Direct link
Cite
Citation style
  • apa
  • harvard1
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Other style
More styles
Language
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Other locale
More languages
Output format
  • html
  • text
  • asciidoc
  • rtf
v. 2.28.0