Water distribution tests using Extended Coverage sprinklers for the Muskö Tunnel
RISE - Research Institutes of Sweden, Safety and Transport.
RISE - Research Institutes of Sweden, Safety and Transport.
2017 (English)Report (Other academic)
Abstract [en]

The objective of the tests was to determine the water distribution characteristics using different water pressures and sprinkler spacing of two selected Extended Coverage sprinklers. The sprinklers may be used for the protection of the Muskö tunnel and the test set‑up simulated a freight truck trailer positioned inside the tunnel.

Adequate sprinkler coverage would require that sprinklers are positioned close to the peak of the ceiling. A relatively short vertical distance from the sprinklers and the ceiling is also essential for proper thermal activation. These requirements are best met by the use of upright sprinklers. Two extended coverage upright sprinklers with a K‑factor of 363 (metric) and 202 was selected for the tests.

For the extended coverage upright K363 sprinkler (Tyco model EC‑25), a sprinkler spacing of 4.0 m is recommended, in order to account for the fact that full coverage of the freight truck trailer was not achieved at the tested 4.2 m spacing. A density of 10 mm/min requires an operating pressure of around 0.7 bar at this particular spacing.

The tested extended coverage upright K202 sprinkler (Tyco model EC‑14) provided a wider water discharge pattern, with a proper water distribution on the top of a freight truck trailer positioned offset in the tunnel at sprinkler spacing up to 5.0 m. For an actual installation, a K202 sprinkler designed for a density of 10 mm/min require an operating pressure of around 3.6 bar at this particular spacing.

Place, publisher, year, edition, pages
2017. , 31 p.
Series
RISE Rapport, 2017:52
Keyword [en]
Tunnel fire, automatic sprinklers, extended coverage sprinklers, water distribution
National Category
Other Engineering and Technologies
Identifiers
URN: urn:nbn:se:ri:diva-32609OAI: oai:DiVA.org:ri-32609DiVA: diva2:1155983
Funder
Swedish Transport AdministrationSwedish Nuclear Fuel and Waste Management Company, SKB
Available from: 2017-11-10 Created: 2017-11-10 Last updated: 2017-11-10Bibliographically approved

Open Access in DiVA

RISE Report 2017_52(3355 kB)4 downloads
File information
File name FULLTEXT01.pdfFile size 3355 kBChecksum SHA-512
5fd3d9d16811c2994aade8567655f791c8a9702a39ede11fc83defd6dfa6ce1fe2628ba1280aeef3821335daa2f23ae915a78c1c3fab05f9b41b3340de64d62c
Type fulltextMimetype application/pdf

By organisation
Safety and Transport
Other Engineering and Technologies

Search outside of DiVA

GoogleGoogle Scholar
Total: 4 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

Total: 30 hits
CiteExportLink to record
Permanent link

Direct link
Cite
Citation style
  • apa
  • harvard1
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Other style
More styles
Language
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Other locale
More languages
Output format
  • html
  • text
  • asciidoc
  • rtf
v. 2.28.0