Down-time corrosion in boilers
RISE., SP – Sveriges Tekniska Forskningsinstitut, SP Energi och Bioekonomi.
RISE., SP – Sveriges Tekniska Forskningsinstitut, SP Energi och Bioekonomi.
RISE., SP – Sveriges Tekniska Forskningsinstitut, SP Energi och Bioekonomi.
2016 (engelsk)Inngår i: Fuel processing technology, ISSN 0378-3820, E-ISSN 1873-7188, Vol. 141, s. 276-284Artikkel i tidsskrift (Fagfellevurdert) Published
Abstract [en]

Down-time corrosion can occur on boiler surfaces, e.g. furnace walls, superheaters, or economizers that are covered with hygroscopic deposits, when the temperature drops under 100 °C. This scenario takes place when a boiler is shut-down for cleaning, maintenance, or other reasons, such as unplanned shut-downs. Initially, the dry deposits will absorb moisture from the surrounding air, potentially creating a corrosive environment. After this, corrosive acids can form in the deposits. In this study modified online-corrosion probes were used in combination with deposits taken from 6 different boilers at various locations (for example, from the furnace, the superheater, and the economizer), where the fuels have been waste, demolition wood or biomass. The deposits were ground and dried in an oven at 160 °C for several hours before exposed to a moist environment (RH 65%) during online measuring of the corrosion rate and the pitting activity. Four types of alloys were tested: low-alloy ST45.8-steel, 9% Cr ferritic P91-steel, austenitic stainless steel 304L, and Ni-based super Alloy 625. The results for ST45.8 show that in biomass boilers a corrosion rate from negligible values up to 0.7 mm/year can be reached within a week, while waste-fired boilers can have rates as high as 1.8 mm/year. Furthermore, for some samples from waste-fired boilers show a high pitting activity already after 24 h. The tests with the P91-steel show values up to 0.16 mm/year, for samples from different locations in the boiler. For 304L and Alloy 625 the down-time corrosion was negligible even after a two-week exposure. The ability to follow the down-time corrosion online has provided data that show that even though thought to be negligible, the risk of down-time corrosion is of significance, especially if the fuel is waste. Also, even if the initial corrosion rate is low, it increases during the first 24 h due to the exposure to moist environment, motivating immediate cleaning of the boilers after shut-down, especially on surfaces of lower steel quality.

sted, utgiver, år, opplag, sider
Elsevier, 2016. Vol. 141, s. 276-284
Emneord [en]
Down-time corrosion, Online-corrosion probe, Deposits
HSV kategori
Identifikatorer
URN: urn:nbn:se:ri:diva-409DOI: 10.1016/j.fuproc.2015.10.009Scopus ID: 2-s2.0-84948458541OAI: oai:DiVA.org:ri-409DiVA, id: diva2:941648
Tilgjengelig fra: 2016-06-22 Laget: 2016-06-22 Sist oppdatert: 2020-12-01bibliografisk kontrollert

Open Access i DiVA

Fulltekst mangler i DiVA

Andre lenker

Forlagets fulltekstScopus
Av organisasjonen
I samme tidsskrift
Fuel processing technology

Søk utenfor DiVA

GoogleGoogle Scholar

doi
urn-nbn

Altmetric

doi
urn-nbn
Totalt: 196 treff
RefereraExporteraLink to record
Permanent link

Direct link
Referera
Referensformat
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Annet format
Fler format
Språk
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Annet språk
Fler språk
Utmatningsformat
  • html
  • text
  • asciidoc
  • rtf
v. 2.41.0