Model scale tunnel fire tests with automatic sprinkler
RISE., SP – Sveriges Tekniska Forskningsinstitut, SP Fire Research.ORCID-id: 0000-0001-7744-2390
RISE., SP – Sveriges Tekniska Forskningsinstitut, SP Fire Research, Branddynamik.ORCID-id: 0000-0002-9340-6768
2013 (engelsk)Inngår i: Fire safety journal, ISSN 0379-7112, E-ISSN 1873-7226, Vol. 61, s. 298-313Artikkel i tidsskrift (Fagfellevurdert) Published
Abstract [en]

Abstract The study focuses on the performance of an automatic sprinkler system in a model scale tunnel with longitudinal ventilation. A total of 28 tests were carried out in a 1:15 model scale tunnel using an automatic sprinkler system with glass bulbs. The maximum heat release rate, energy content and failure of the automatic sprinkler system were analysed. The results show that high ventilation rates and low water flow rates result in a failure of the automatic sprinkler system in a longitudinal ventilated tunnel fire. The main reason for the failure under the tested water flow rates was the effect of the longitudinal flow on the fire development and the hot gas flow close to the sprinklers. The fire development and the activation heat release rate of the first activated bulb are intimately related to the ventilation velocity. The fire spread to the neighbouring wood crib was investigated and a presentation of tests conducted using a deluge system are given.

sted, utgiver, år, opplag, sider
2013. Vol. 61, s. 298-313
Emneord [en]
Automatic sprinkler, Keywords, Model scale tests, Tunnel fire, Ventilation, Longitudinal ventilation, Maximum heat release rate, Model scale, Model scale tunnels, Tunnel fires, Ventilation velocity, Flammability testing, Flow of water, Flow rate, Hose, Hydraulics, Sprinkler systems (fire fighting), Sprinkler systems (irrigation)
HSV kategori
Identifikatorer
URN: urn:nbn:se:ri:diva-48623DOI: 10.1016/j.firesaf.2013.09.024Scopus ID: 2-s2.0-84886723403OAI: oai:DiVA.org:ri-48623DiVA, id: diva2:1473011
Merknad

This project was sponsored by the Swedish Fire Research Board (BRANDFORSK) and the SP Tunnel and Underground Safety Centre which are greatly acknowledged. The technicians Sven-Gunnar Gustafsson, Tarmo Karjalainen and Michael Magnusson at SP Fire Technology are acknowledged for the construction of the test rig and the assistance during performance of the tests. Thanks also to Jonatan Gehandler and Hans Nyman for their help during the tests.

Tilgjengelig fra: 2020-10-05 Laget: 2020-10-05 Sist oppdatert: 2023-06-08bibliografisk kontrollert

Open Access i DiVA

Fulltekst mangler i DiVA

Andre lenker

Forlagets fulltekstScopus

Person

Li, Ying ZhenIngason, Haukur

Søk i DiVA

Av forfatter/redaktør
Li, Ying ZhenIngason, Haukur
Av organisasjonen
I samme tidsskrift
Fire safety journal

Søk utenfor DiVA

GoogleGoogle Scholar

doi
urn-nbn

Altmetric

doi
urn-nbn
Totalt: 64 treff
RefereraExporteraLink to record
Permanent link

Direct link
Referera
Referensformat
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Annet format
Fler format
Språk
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Annet språk
Fler språk
Utmatningsformat
  • html
  • text
  • asciidoc
  • rtf
v. 2.43.0